HomeMy WebLinkAboutCHAPTER 55 CHAPTER 55. FIRE PREVENTION
───────────────────────────────────────────────────────────────────
Updated 2018 55-1
55. FIRE PREVENTION
55.01. Fire Code. Subdivision 1. The Minnesota State Fire Code adopted by the
State Fire Marshal pursuant to Minnesota Statutes Section 299F.011, July 10, 2007,
Minnesota Rules Chapter 7511.0010 to 7511.8570, and Appendix A, B, C, and D of the
International Fire Code, 2006 Edition, promulgated by the International Fire Code Institute, are
hereby adopted as the fire code for the City of Rochester, except as modified in this code.
The aforesaid fire code of the city of Rochester shall be known as and may be cited as the
"Fire Code". Any provision of the Fire Code to protect life or property in the city which is more
restrictive shall prevail over the provisions of the Minnesota State Fire Code.
Subd. 2. In addition to those provisions described in Subdivision 1 hereto, the Fire
Code shall require that the following uses of a building or premises, as otherwise more
specifically described in Section 105.6 of the International Fire Code, 2006 Edition,
promulgated by the International Fire Code Inc., shall require the following operational permits
from the Bureau of Fire Prevention to be prominently displayed on the premises and kept on
file in the office of the city clerk for examination and use by the public:
1. Amusement buildings; 105.6.2
2. Aviation facilities; 105.6.3
3. Miscellaneous combustible storage; 105.6.29
4. Combustible dust producing operations; 105.6.6
5. Combustible fibers; 105.6.7
6. Compressed gases; 105.6.8
7. Cryogens; 105.6.10
8. Cutting and Welding; 105.6.11
9. Dry cleaning plants; 105.6.12
10. Exhibits and trade shows; 105.6.13
11. Fireworks displays, public; 3301.2.4.2
12. Flammable/combustible liquid storage, use and tank installation; 105.6.16
13. Hazardous materials; 105.6.20
14. HPM Facilities; 105.6.21
15. High piled storage; 105.6.22
16. Hot-work operations; 105.6.23
17. Liquid petroleum gases; 106.6.27
18. Liquid or gas-fuel vehicles or equipment in assembly buildings; 105.6.26
19. Lumberyards and woodworking plants; 105.6.25
20. Mall, covered; 105.6.9
21. Open burning; 105.6.30
CHAPTER 55. FIRE PREVENTION
───────────────────────────────────────────────────────────────────
Updated 2018 55-2
22. Place of assembly; 105.6.34
23. Pyrotechnic special effects; 105.6.36
24. Repair/maintenance/installation garages; 105.6.39
25. Spraying or dipping operations; 105.6.41
26. Tents, air supported structures, canopies; 105.6.43
27. Tire storage; 105.6.42
28. Tire rebuilding plants; 105.6.44
29. Waste handling; 105.6.45
30. Wood product; 105.6.46
Subd. 3. In addition to those provisions described in Subdivision 1 and 2 the Fire Code
shall require a Special Fire Department Permit be obtained by the installing contractor of all
new installations or modifications of private fire service water mains, automatic sprinkler, fire
alarm, automatic chemical extinguishing systems, alternative fire protection systems and
flammable or combustible liquid or hazardous materials tanks within the City of Rochester
and/or all such installations which the Rochester Fire Department is responsible for plan
review, on site inspection, and approvals.
Subd. 4. All such installations or modifications shall be performed by contractors
properly licensed under Minnesota Rule 7512, 7105, Minnesota Statutes Section 326.2421 or
as required by any other governmental agency. Proof of valid license or certification shall
accompany all applications for permit.
Subd. 5. Fees: Fire Protection Equipment Permit Fees. Fees for each permit shall be
charged to perform necessary plan reviews of affected installations. Permit fees shall be the
actual cost of the labor and components of the fire protection system or tank installation
project multiplied by .015 or a minimum of $50. When applying for the permit, the contractor
shall pay an estimated fee based on the estimated cost of the project. If the actual cost of the
project is greater than the estimated cost, the contractor shall pay any additional fee amount
before the final acceptance test. It is the contractor's responsibility to submit all required
surcharge fees due to the Commissioner of Public Safety directly to the Commissioner.
Subd. 6. Work Without a Permit: When substantial work on installations subject to this
subdivision is determined to have been commenced without benefit of the required Special
Fire Department Permit and associated plan reviewal, a special inspection of the site by a fire
department inspector, shall be made as determined by the Fire Marshal before a permit may
be issued for that installation. A separate fee will be assessed for the project equal to the
normal Fire Protection Equipment Permit Fee up to a maximum of $150.
CHAPTER 55. FIRE PREVENTION
───────────────────────────────────────────────────────────────────
Updated 2018 55-3
Subd. 7. On-site and After Hours Inspection Fees. A fee will be charged for all
required on-site inspections of permitted Fire Protection Equipment permitted installations and
inspections which occur outside the hours of 08:00 am through 05:00 pm Monday through
Friday will be billed to the installing contractor according to the hourly rate in the current
employment contract of the responding Fire Department personnel.
Subd. 8. Special Inspections. Special inspections of Fire Protection System
installations may be required by the Fire Marshal when necessary to ascertain compliance
with the provisions of the Fire Code and NFPA standards enforced in conjunction with
required installations. All special inspections shall be completed prior to Fire Department final
inspection, final approval or Certificate of Occupancy issuance. Installing contractors of fire
protection equipment are responsible to provide documentation of completed required
inspections and witnessing of all required tests as performed by an approved and qualified
independent inspector or engineer, in accordance with the Building Code Section 109 and
Fire Code Section 104.7.2 Qualified inspectors shall meet the minimum qualifications as
determined by the Fire Chief.
Subd. 9.Pursuant to section 901.6.2 of the Fire Code, contractors who perform
inspection, testing and/or maintenance services on fire and life safety systems within the City
of Rochester are required to electronically submit all compliant and non-compliant reports to
the Rochester Fire Department using the method approved by the Fire Chief. (4133, 11/4/13)
55.02. Modifications. Subdivision 1. General. The Fire Code described in Section
55.01 is subject to the modifications contained in this section.
Subd. 2. Jurisdiction. The word "jurisdiction" when used in the Fire Code shall mean
the City of Rochester.
Subd. 3. Corporation Counsel. The term "corporation counsel" when used in the Fire
Code shall mean the city attorney.
Subd. 4. Police Enforcement Assistance. Whenever requested to do so by the Chief
of the Fire Department, the Chief of Police shall assign such available police officers as the
Chief of Police may deem necessary to assist the fire department in enforcing the provisions
of the Fire Code.
Subd. 5. Police Investigation Assistance. The police department shall assist the fire
department in its investigations whenever requested to do so, unless otherwise directed by
the Chief of Police.
CHAPTER 55. FIRE PREVENTION
───────────────────────────────────────────────────────────────────
Updated 2018 55-4
Subd. 6. Filling Gas Tanks. No person shall fill or partly fill any gasoline tank of any
motor vehicle upon any street, alley, or public ground from any gasoline tank wagon, truck, or
any moving vehicle used for the sale or transportation of gasoline for commercial purposes.
Subd. 7. Overcrowding. Overcrowding and admittance of persons beyond the
approved maximum, posted occupant load capacity, as required by IFC Sec. 1004.3 for a
place of assembly is prohibited. When overcrowding is determined to have occurred, the Fire
Chief is authorized to cause the performance, presentation, spectacle or entertainment to be
stopped until such time as the overcrowded condition is corrected.
Subd. 8. Hydrant Height. All required fire hydrants shall be positioned so the distance
from the adjacent grade level is not less than 30" to the top of the hydrant and the 4" outlet
shall face the roadway and/or curb line.
Subd. 9. All required fire alarm systems in new buildings shall be monitored and
supervised by a central station monitoring company acceptable to the Chief of the Fire
Department, a proprietary supervising system or a remote supervising station system. By
January 1, 2011, all required fire alarm systems in existing buildings shall be monitored and
supervised as required for new buildings.
Subd. 10. Notwithstanding anything in subdivision 9 to the contrary, monitoring and
supervisory service is not required for single and multiple station smoke alarms required by
section 907.2.10 of the Minnesota State Fire Code or automatic sprinkler systems in one and
two family dwellings.
55.03. Storage of Explosives. The storage of explosives for which a license or the
possession of which a permit is required under state law is prohibited within the corporate
limits of the city, except for temporary storage in connection with use for approved blasting
operations. Persons conducting blasting operations under a valid permit issued by the Chief of
Police or Sheriff.
55.04. Fireworks and Pyrotechnic Displays. Fireworks and pyrotechnic displays shall
be limited to those intended specifically for public viewing outdoors and as are permitted
pursuant to Minnesota Statutes Section 624.20 and Chapter 33 of the Fire Code. Indoor
pyrotechnic displays are permitted only in buildings protected throughout by an approved
automatic fire sprinkler system. Public fireworks and pyrotechnic displays require application
to the City Clerk’s office for approval by the Common Council prior to conducting the display.
CHAPTER 55. FIRE PREVENTION
───────────────────────────────────────────────────────────────────
Updated 2018 55-5
55.05. Storage of Flammable or Combustible Liquids. Subdivision 1. Class I and II
Flammable Liquids. The storage of class I and II flammable liquids in above-ground tanks
outside of buildings is prohibited in all parts of the city except those areas zoned M-2 general
industrial district pursuant to this code. This section shall not apply to commercial installations
not intended for public use and installed as provided in the Fire Code Chapter 22.
Subd. 2. New Bulk Plants. New bulk plants for flammable or combustible liquids are
prohibited in all parts of the city except those areas zoned M-2 general industrial district
pursuant to this code.
55.06. Bulk Storage of Liquefied Petroleum Gases. The storage of liquefied petroleum
gases is prohibited in all parts of the city except those areas zoned M-2 general industrial
district pursuant to this code.
55.07. Permits. Subdivision 1. Permits issued under Subd 2 and the fire code shall be
valid for the period of one year or such lesser period as is designated in the permit. If the
activity or purpose for which a permit is issued is a continuing nature, a new permit shall be
obtained annually on or before the anniversary date of the permit last issued. A permit fee of
$55.00 for each permitted activity and $10 for each additional permitted activity at the same
property, facility or building shall be charged for each permit issued, including each annual
renewal thereof.
Subd. 2. Open burning permits issued under section 55.01, subdivision 1 and the Fire
Code shall be valid for a period of 30 days or such time period as designated in the permit. If
the authorized burning activity continues for greater than 30 days, the permit may be
extended for an additional 30 days at the discretion of the Fire Marshal. A permit fee of
$150.00 for each open burning permit shall be charged per location.
55.08 Appeals. Subdivision 1. All requests for appeals shall be made to the Fire
Chief within the time designated in the correction order and will be forwarded to the Board of
Appeals for a hearing as provided in Chapter 33.
Subd. 2. An application for appeal shall be based on a claim that the intent of this code
or the rules legally adopted thereunder have been incorrectly interpreted, the provisions of this
code do not fully apply, or an equivalent method of protection or safety is proposed. The
Board does not have the authority to waive requirements of the Fire Code.
Subd. 3. Any person may appeal an order issued to them on issues regulated by the
Rochester Fire Code. This appeal shall be forwarded to the Board of Appeals established by
chapter 33. (4357, 10/1/18)
CHAPTER 55. FIRE PREVENTION
───────────────────────────────────────────────────────────────────
Updated 2018 55-6
55.09. Violations. Any violation of any provision of the fire code or failure to comply
therewith, or violation or failure to comply with any order made thereunder, or any building in
violation of any specifications or plans submitted and approved thereunder or in violation of
any certificate or permit issued to thereunder, and from which no appeal has been taken, or
failure to comply with such order as affirmed or modified by the council herein, shall be a
separate violation. The imposition of one penalty for any violation shall not excuse the
violation or permit it to continue, and any person responsible for the violation shall correct or
remedy such violation or defect within a reasonable time. When not otherwise specified, each
day that prohibited conditions are maintained shall constitute a separate offense. The
application of any penalty shall not be held to prevent the enforced removal of prohibited
conditions.
55.10. Failure to Comply. Fire Code Sub. “Section 111.4 Failure to Comply” is
amended to read: “Any person who shall continue any work after having been served with a
stop work order, except such work as that person is directed to perform to remove a violation
or unsafe condition, shall be guilty of a misdemeanor.”
55.11. Re-inspection Fee. When in the course of enforcing a duly issued violation
notice, it becomes necessary for a Fire Department Inspector to make one or more additional
return visit(s) to re-inspect a property, over and above the normal one follow-up inspection, to
insure compliance to the fire code, a "re-inspection" fee of $55.00 will be charged to the
property/business owner for each additional re-inspection required to obtain compliance.
55.12. Fire Response Reimbursement. Persons determined responsible for malicious
false alarms resulting in an unnecessary fire department response will be required to
reimburse the fire department for the actual cost of that run, in addition to any court ordered
fines or charges. Minimum charges will be determined by the actual hourly rates, according to
the current employment contract, of the responding Fire Department personnel and the
following hourly rates for responding apparatus and vehicles used: Chief’s Car: $50 per hour;
Engine: $75 per hour; Aerial: $95 per hour; Rescue: $50 per hour; Fire Investigation: $50
per hour.
CHAPTER 55. FIRE PREVENTION
───────────────────────────────────────────────────────────────────
Updated 2018 55-7
55.13. Fire Department Standby Charges. When required by the Fire Code or when
requested by outside agencies to provide “standby” fire department personnel to perform fire
safety, inspection or other fire related duties, the Fire Department must charge that agency or
business for the actual cost of providing those standby personnel and vehicles. Minimum
charges will be as stated in section 55.12.
(173, 5/12/03; 224, 9/27/16; 269, 9/23/19; 318, 8/16/22; 852, 10/5/53; 1321, 9/7/65; 1388,
1/16/67; 1429, 11/20/67; 1832, 2/17/76; 2218, 11/17/81; 2341, 12/6/83; 2343, 12/19/83; 2387,
6/19/84; 2625, 4/4/89; 2763; 9/17/91; 2960, 12/20/94; 3023, 3/19/96; 3211, 12/8/98; 3582,
8/4/03; 3878, 7/21/08; 3955, 2/1/10; 4133, 11/4/13; 4357, 10/1/18)